Description
Features
Reviews
Surge arrester T3 3P+N Uc 264V In 3kA Up 1.4kV contact. Device protection type 3 for 5-wire systems (L1, L2, L3, N, PE) consisting of protective plug and base element for DIN rail mounting. Optical red/green status display and remote signaling contact for error signaling. Integrated, surge current-proof fuses for electrical and thermal overload. Plug with individual labeling area, can be plugged and unplugged without tools and protected against incorrect assembly by mechanical coding.
Property | Value |
Protection level: | 1.4 kV |
Nominal voltage AC: | 230 V |
Nominal voltage DC: | 230 V |
Maximum continuous voltage AC: | 264 V |
Mounting type: | DIN rail TH35 |
With remote signaling contact: | no |
Nominal discharge current (8/20) (LN): | 9 kA |
Total discharge current (8/20) (L+N-PE): | 9 kA |
Nominal load current: | 26 A |
Protection level LN: | 1.25 kV |
Protection level L-PE/N-PE: | 1.4 kV |
Number of poles: | 4 |
Signaling on the device: | optical |
Test class type 3: | yes |
Max. conductor cross-section rigid (single/multi-wire): | 4 mm² |
Max. conductor cross-section flexible (fine-stranded): | 2.5 mm² |
Protection class (IP): | IP20 |
Total discharge current (8/20) (L1+L2+L3+N-PE): | 9 kA |
Features
Max. conductor cross-section rigid (single/multi-wire)
4 mm²
Max. conductor cross-section flexible (fine-stranded)
2.5 mm²
Protection level
1.4 kV
With remote signaling contact
No
Nominal load current
26 A
Nominal voltage DC
230 V
Protection level L-N
1.25 kV
HAB
SPC403N T3 3P+N Uc 264V In 3kA Up 1.4kV
Manufacturer
HAN
SPC403N
GTIN
3250615514943
Highest continuous voltage AC
264V
Mounting type
DIN rail TH35
Nominal voltage AC
230V
Number of poles
4
IP protection)
IP20
Signaling on the device
Optical
No reviews yet — your comment may be first.
All reviews 0