UMG 96-PA energy meter with clock, battery and measurement data memory (4MB), front panel installation device: 96 x 96 x 86 mm (WxHxD), supply voltage: 90 V - 277 V (50/60 Hz) or 90 V - 250 V DC, installation category: 300 V CAT III, measurement in TN and TT networks, measurement of harmonics up to the 25th, active energy class 0, 2S, voltage measurement inputs: measurement category: 600 V CAT III, measurement in 3-phase 4-wire systems up to 417 V/720 V (+-10%) according to IEC, measurement in 1-phase 2-wire systems up to 480 V (+-10%), 3 current measurement inputs: measurement category: 300 V CAT II, nominal current 5A / 1A adjustable, current measurement range: 5 mA... 6 A, resolution: 0, 1mA, peripherals: 3x digital inputs and outputs each, 1x analog output, 1x RS485 (Modbus RTU), accessories (included): 33.03.375 installation instructions including safety instructions and GridVis® quick start software, 52.22.251 mounting kit, 52.00.008 RS485 terminating resistor 120 Ohm, GridVis® Basic programming software,
Property | Value |
Display: | graphical |
Number of voltage input channels: | 3 |
Number of current input channels: | 3 |
Current measurement: | direct current measurement |
Harmonics measurement: | yes |
Power factor: | yes |
Active power: | yes |
Reactive power: | yes |
Apparent power: | yes |
Phase angle (cos phi): | yes |
Power/work: | yes |
Interface: | yes |
Measurement value memory: | yes |