UMG 96RM-E energy meter with Ethernet and RCM, (UL) supply voltage 24V..90V (50/60Hz), 24V..90V DC, 150V CATIII voltage measurement, measurement category 300V CATIII, 3 voltage measurement inputs (LN: 20V-300V, LL: 34V- 520V, 45Hz-65Hz), 3+1 current measurement inputs 0..5A, response current 5mA, measurement in three-phase 4-wire systems with grounded neutral conductor up to max. 277V/480V, measurement in ungrounded three-phase 3-wire systems up to max. 480V, measurement in single-phase 3-wire systems up to max. 220V-440V, measurement in single-phase 2-wire systems up to max. 220V, 2 digital outputs3 digital inputs/outputs, configurable2 analogue inputs, optionally also as temperature or differential current measurement input (RCM)Clock and data memory (256 MB Flash), homepage, interfaces: Ethernet, RS485 Protocol: TCP/IP, Modbus RTUAccessories (included):33.03.220 Installation instructions, safety instructions and GridVis quick start software52.22.251 Mounting kit 08.01.505 Patch cable 2 m, twisted, grey52.00.008 RS485 terminating resistor 120 Ohm, programming software GridVis Basic download: www.janitza.de/gridvis-download.html
Property | Value |
Display: | digital |
Number of Voltage input channels: | 3 |
Number of current input channels: | 4 |
Current measurement: | direct current measurement |
Harmonics measurement: | yes |
Power factor: | yes |
Active power: | yes |
Reactive power: | yes |
Apparent power: | yes |
Phase angle (cos phi): | yes |
Power/Work: | yes |
Interface: | yes |
Measured value memory: | yes |