Universal relay station 8-way REG housing 8 TE
with electronic manual operation and LED status display
8 normally open contacts
Intended use
Switching lighting
Switching single-phase fan motors
Switching electrically operated blinds, roller shutters, awnings and similar hangings
Installation on top hat rail in sub-distribution board
Operation using sensor modules, touch sensor modules or unlit installation buttons
Product features
On-site operation: the relay station can be operated using the keypad without any control points being connected.
Control of feedback LEDs on the control points. The relay station has control outputs A1' ... A8' for this purpose.
Switch operation
Touch operation
Blind operation with slat adjustment
Mixed operation of switching, touching and blinds is possible
Central function Central ON, Central OFF: Switching the load outputs on or off together
Parallel connection of two relay stations possible
Nominal voltage: AC 230/240 V ~, 50/60 Hz
Power loss: 12.5 W
Standby power: 0.5 W
Length of control cable: max. 100 m
Number of control points
Sensor module (item no.: SM 1608): max. 4 (also for relay/dim stations connected in parallel)
Touch sensor modules 24 V AC/DC (normally open): depends on the touch sensor module, current consumption note
Touch sensor module (item no.: 4008 TSM): max. 4 (also with relay/dim stations connected in parallel)
Control points
Voltage: DC 24 V SELV
Current load: 80 mA
Switching inputs E1 ... E8
Resistance Ri: 200 k
Control voltage: DC 24 V SELV
Control outputs A1' ... A8'
Resistance Ra: 330
Control voltage: DC 24 V SELV
Current load: 10 mA
Connection mains and load outputs
Connection type: screw terminals
single-wire: 1 x 1.5 ... 4 mm2
fine-wire without wire end sleeve: 1 x 0.75 ... 4 mm2
fine-wire with Wire end ferrule: 1 x 0.5 ... 2.5 mm2
Connection of switching inputs / control outputs / control points
Connection type: screw terminals
single-wire: 1.5 mm²
fine-stranded without wire end ferrule: 1 mm²
fine-stranded with wire end ferrule: 0.75 mm²
Load outputs A1 ... A8
Contact type: potential-free normally open contact (-contact)
Switching capacity per load output: AC 250 V ~ / 16 AX
Switching current of load outputs: 80 A
Switching current of adjacent load outputs: 20 A
Loads per output
Ohmic load: 3000 W
Capacitive load: 16 A / max. 140 µF
Blind/fan motors: 1380 VA
Inrush current: max. 800 A (200 µs)max. 165 A (20 ms)
Lamp loads
Incandescent lamps: 3000 W
HV halogen lamps: 2500 W
LV halogen lamps with
electronic transformers: 1500 W
inductive transformers: 1200 VA
Fluorescent lamps
uncompensated: 1000 W
parallel compensated: 1160 W / 140 µF
Duo circuit: 2300 W / 140 µF
Electronic ballast: type-dependent
Minimum load: AC 12 V, 100 mA
Ambient temperature: 5 ... +45 °C
Storage temperature: 25 ... +70 °C
Installation width: 144 mm (8 TE)
Locking time for change of direction: 1 s
Duty cycle for blind operation: 2 min
Property | Value |
Mounting type: | DIN rail |
Control voltage type 1: | DC |
Control voltage 1: | 24.0 V |
Max. fluorescent lamp load: | 1000 VA |
Max. Switching current (cos phi = 0.6): | 16 A |
Function: | partially electronic |
Width in modular spaces: | 8 |
Max. incandescent lamp load: | 3000 W |
Max. fluorescent lamp load (parallel compensated): | 1160 VA |
Max. Fluorescent lamp load (duo circuit): | 2300 VA |
Supply voltage: | 230.0 to 240.0 V |
Control voltage 2: | 24 V |
Control voltage type 2: | DC |
Voltage type of supply voltage: | AC |
Number of contacts as normally open: | 8 |