Plant engineering, mechanical engineering, heating and air conditioning technology, machine tools, Mainly in dry, damp and wet rooms (including water-oil mixtures), but not outdoors, Fixed installation as well as occasional flexible use with free, not constantly recurring movement without tensile load or forced guidance and medium mechanical stress, Note: Use of cables of type AWM (Appliance Wiring Material) in industrial machines (USA) according to NFPA 79 Ed. 2015: see catalog appendix Table T29, High electrical safety due to 4 kV test voltage, Versatile application possibilities, Fine-wire strand made of bare copper wires, PVC core insulation, Sheath: PVC, increased oil resistance, gray (similar to RAL 7001), Cores twisted in layers, Multi-standard cables are designed in metric nominal cross-sections in mm² or AWG/kcmil nominal sizes. The leading cross-section is given in the table below, the corresponding cross-section of the other system is from catalog appendix table T16, UL AWM Style 21098 CSA AWM IA/B II A/B, flame-retardant according to IEC 60332-1-2 and UL 1581 §1061 Cable Flame Test, oil-resistant according to EN 50363-4-1: TM5,
| Property | Value |
| Number of cores: | 7 |
| Nominal conductor cross-section: | 1 mm² |
| Sheath color: | gray |
| Outer diameter approx.: | 8.8 mm |
| Conductor class: | Cl.5 = fine-wire |
| Stranding element: | no |
| Material of the core insulation: | Polyvinyl chloride (PVC) |
| Core marking: | numbers |
| Protective conductor: | yes |
| Shield over stranding element: | without |
| Shield over stranding: | without |
| Support element: | without |
| Sheath material: | Polyvinyl chloride (PVC) |
| Torsion protection: | no |
| Halogen-free according to EN 60754-1/2: | no |
| Flame-retardant: | according to EN 60332-1-2 |
| Low smoke according to EN 61034-2: | no |
| Cold-resistant according to EN 60811-504+505+506: | yes |
| Oil resistant according to EN 60811-404: | yes |
| Permissible external cable temperature during assembly/handling: | -5 to 70 °C |
| Permissible Cable external temperature after installation without vibration: | -40 to 70 °C |
| Nominal voltage U0: | 300 V |
| Nominal voltage U: | 500 V |
| Shape: | round |
| Min. permissible bending radius, flexible use/free movement: | 132 mm |
| Min. permissible bending radius, stationary use/fixed installation: | 35.2 mm |