Connection cable between frequency converter and motor, paper industry, chemical industry, heavy industry, in dry, damp and wet rooms, EMC-compliant construction of speed-controlled electrical drives in accordance with EN 61800-3, high power transmission for large drives, earth-symmetrical 3+3 version supports the reduction of bearing currents, version 9YSLCY black: also outdoors or directly in the ground, but not in the USA or Canada, longer cable lengths between converter and drive possible due to low-capacitance construction, fine-stranded, bare copper conductor, core insulation: polypropylene (PP), cores concentrically stranded (symmetrical thirded protective conductor in 3+3 version is divided between the power cores to fill the gaps), shielding: aluminum-clad foil wrapping combined with tinned copper braid, 4-core version: transparent PVC outer jacket, 3+3 core version: PVC outer jacket, black, USA: AWM Style 2570 or 20886, 1kV 80°C VW-1 Canada: AWM I/II A/B 1kV 80°C FT1, UL File No. E63634, based on 0276, 0250, 0207, EN/VDE +90° C PP insulation, flame retardant in accordance with IEC 60332-1-2 & CSA FT1,
Property | Value |
Main conductor nominal cross-section: | 120 mm² |
Outer diameter approx.: | 42.6 mm |
Sheath colour: | black |
Number of main cores: | 3 |
Design: | round |
Material of the core insulation: | Polyolefins |
Main core identification: | Color |
Nominal cross-section of auxiliary conductor: | 16 mm² |
Number of auxiliary conductors: | 3 |
Protective conductor: | yes |
Support element: | without |
Torsion protection: | no |
Sheath material: | Polyvinyl chloride (PVC) |
Flame retardant: | according to EN 60332-1-2 |
Permissible external cable temperature during assembly/handling: | -5 to 90 °C |
Permissible Cable external temperature after installation without vibration: | -40 to 90 °C |
Nominal voltage U0: | 0.6 kV |
Nominal voltage U: | 1 kV |
Oil resistant according to EN 60811-404: | yes |
AWG size main conductor: | 0000 |
Main conductor nominal cross-section (AWG): | 0000 kcmil |
Specification of conductor insulation: | other |
Nominal cross-section of auxiliary conductor (AWG): | 6 |
Specification of sheath material: | other |
Min. permissible bending radius, flexible use/free movement: | 639 mm |
Min. permissible bending radius, stationary use/fixed installation: | 170.4 mm |