Areas with high ambient temperatures in which conventional wire insulation materials become brittle after a short time, typical areas of application - switch cabinet construction - device and apparatus construction - electric motor industry - sauna and solarium construction - heat and heating elements - lighting technology - fan construction - air conditioning technology - furnace construction - plastics processing - generators and, after exposure to flames, the SiO2 ash structure remaining has insulating properties, fine-stranded, tinned copper conductor, silicone-based insulation, halogen-free according to IEC 60754-1 (proportion of halogen acid-containing gases) corrosiveness of the combustion gases according to IEC 60754-2 (acidity level), resistant to a variety of oils, alcohols, vegetable and animal fats and other chemical media, flame-retardant according to IEC 60332-1-2, Sufficient ventilation must be ensured, since the mechanical properties of silicone cables deteriorate prematurely from +100°C in the absence of air. reduce,
Property | Value |
Number of cores: | 1 |
Conductor nominal cross-section: | 1.5 mm² |
Outer diameter approx.: | 2.8 mm |
Core marking: | Color |
Material of core insulation: | Rubber |
Sheath color: | without |
Sheath material: | without |
Protective conductor: | yes |
Nominal voltage U0: | 300 V |
Nominal voltage U: | 500 V |
Conductor material: | copper |
Conductor class: | Class 5 = finely stranded |
Perm. max. conductor temperature: | 180 °C |
Shield: | no |
Drain wire: | no |
Protective cover: | without |
Reinforcement/armoring: | without |
Halogen-free according to EN 60754-1/2: | yes |
Flame-retardant: | according to EN 60332-1-2 |
Low smoke according to EN 61034-2: | no |
Cold-resistant according to EN 60811-504+505+506: | yes |
Oil-resistant according to EN 60811-404: | no |
Insulation integrity: | no |
Perm. Cable external temperature after installation without vibration: | -50 to 180 °C |
Conductor surface: | tinned |
AWG size: | 16 |
Conductor nominal cross-section (AWG): | 16 kcmil |
Wires twisted: | no |
Fire behavior class according to EN 13501-6: | without |
Smoke development class according to EN 13501-6: | without |
Drip behaviour class according to EN 13501-6: | without |
Acid development class according to EN 13501-6: | without |
Min. permissible bending radius, stationary use/permanently installed: | 16.8 mm |