Typical areas of application: control cabinets with high heat generation - measuring instruments - ovens and brickworks - heating devices and kitchen systems - electric motor construction - installations in chemical engineering, industrial areas in which very high temperatures, aggressive chemical media, but also tight spaces rule out the use of conventional cables, thin outer diameters for maximum space and weight savings, insensitive to most highly aggressive chemical media, fine-wire, tinned copper conductor, FEP wire insulation, FEP = fluoroethylene propylene, ÖLFLEX® HEAT 205 made of FEP - excellent resistance to acids, solvents, paints, petrol, oils and many other chemical media - flame retardant - high dielectric and abrasion resistance - low water absorption - microbe resistant - adhesive, flame retardant according to IEC 60332-1-2,
Property | Value |
Number of cores: | 1 |
Conductor nominal cross-section: | 0.75 mm² |
Core color: | brown |
Outer diameter approx.: | 1.75 mm |
Core marking: | Color |
Core insulation material: | Fluoroethylenepropylene (FEP) |
Sheath color: | without |
Sheath material: | without |
Protective conductor: | no |
Nominal voltage U0: | 300 V |
Nominal voltage U: | 500 V |
Conductor material: | copper |
Conductor class: | Class 5 = finely stranded |
Perm. max. conductor temperature: | 205 °C |
Shield: | no |
Drain wire: | no |
Protective cover: | without |
Reinforcement/armoring: | without |
Halogen-free in accordance with EN 60754-1/2: | no |
Low smoke in accordance with EN 61034-2: | no |
Cold-resistant in accordance with EN 60811-504+505+506: | no |
Oil resistant according to EN 60811-404: | no |
Insulation integrity: | no |
Perm. Cable external temperature after installation without vibration: | -100 to 205 °C |
Conductor surface: | tinned |
AWG size: | 20 |
Conductor nominal cross-section (AWG): | 20 kcmil |
Wires twisted: | no |
Wire insulation specification: | other |
Fire behavior class according to EN 13501-6: | without |
Smoke development class according to EN 13501-6: | without |
Drip behaviour class according to EN 13501-6: | without |
Acid development class according to EN 13501-6: | without |
Min. permissible bending radius, stationary use/permanently installed: | 7 mm |