Industrial machinery, plant engineering, machine tool compliant (UL) MTW, Unprotected 600V operation on cable tray in the USA, including 1.8m exposed run sections, Generatori Eolici in USA: (WTTC) Wind Turbine Tray Cable, Many validations/uses, No need for protection systems: cost-saving, quick installation, Fine-stranded strand made of bare copper wires, Insulation: PVC with nylon sheath (PA skin), Outer jacket: Specially designed thermoplastic polymer, Outer jacket color: Gray, UL OIL RES I/ II, 75°C WET, 90°C DRY, NEC/NFPA 70, NFPA 79, USA: (UL) TC [E171371], -ER > 2 cores, (UL) MTW [E155920], (UL) WTTC [E323700], (UL) THHN/THWN (> 1.5 mm²/16 AWG) [E172162], UL AWM Style 20886 [E100338], CAN: c(UL) CIC/ TC 600V FT4 [E171371], CSA AWM I/II A/B FT1, From June 2018: Sunlight Resistant (Sun. Res.), Direct Burial ( Dir. Bur.), Submersible Pump Cable (> 1.5 mm²/16 AWG, and < 8 conductors), (UL) PLTC (< 6 mm²/10 AWG) [E216027], (UL) ITC (< 6 mm²/10 AWG) [E196134], (UL) DP-1 [E233406], flame retardant according to CSA FT4, Vertical Tray Flame Test, oil resistant according to UL OIL RES I & II, suitable for torsion applications that are typical in the loop of wind turbines (WKA), technically UV and ozone resistant,
| Property | Value |
| Number of cores: | 5 |
| Nominal conductor cross-section: | 2.5 mm² |
| Core colour: | black |
| Outer diameter approx.: | 10.7 mm |
| Core marking: | Numbers |
| Material of Core insulation: | Polyvinyl chloride (PVC) |
| Sheath color: | gray |
| Sheath material: | Polyolefins |
| Protective conductor: | yes |
| Nominal voltage U0: | 600 V |
| Nominal voltage U: | 1000 V |
| Conductor material: | copper |
| Conductor class: | Class 5 = fine-wire |
| Perm. max. conductor temperature: | 90 °C |
| Shield: | no |
| Protective cover: | without |
| Reinforcement/armoring: | without |
| Halogen-free according to EN 60754-1/2: | no |
| Flame-retardant: | according to EN 60332-1-2 |
| Low smoke according to EN 61034-2: | no |
| Oil-resistant according to EN 60811-404: | yes |
| Insulation integrity: | no |
| Permissible external cable temperature during assembly/handling: | -25 to 90 °C |
| Permissible Cable external temperature after installation without vibration: | -40 to 90 °C |
| Conductor surface: | bare |
| Wires twisted: | no |
| Specification of wire insulation: | other |
| Specification of sheath material: | other |
| Min. permissible bending radius, stationary use/permanently installed: | 42.8 mm |