Plant engineering, mechanical engineering, heating and air conditioning technology, In EMC-critical environments (electromagnetic compatibility), Mainly in dry, damp and wet rooms (including water-oil mixtures), but not outdoors, Fixed installation as well as occasional flexible application with free, not constantly recurring movement without tensile load or forced guidance and medium mechanical stress, Note: Use of cables of type AWM (Appliance Wiring Material) in industrial machines (USA) according to NFPA 79 Ed. 2015: see catalog appendix table T29, High electrical safety due to 4 kV test voltage, Wide range of application possibilities, Fine-wire strands made of bare copper wires, PVC core insulation, PVC inner jacket, grey, tinned copper braid, jacket: PVC, increased oil resistance, grey (similar to RAL 7001), cores twisted in layers, Multi-standard cables are designed in metric nominal cross-sections in mm² or AWG/kcmil nominal sizes. The leading cross-section is given in the table below, the corresponding cross-section of the other system is from catalog appendix table T16, UL AWM Style 21098 CSA AWM IA/B II A/B, flame-retardant according to IEC 60332-1-2 and UL 1581 §1061 Cable Flame Test, oil-resistant according to EN 50363-4-1: TM5, high degree of shielding coverage, low coupling resistance (max. 250 /km at 30 MHz),
Property | Value |
Number of cores: | 4 |
Nominal conductor cross-section: | 95 mm² |
Coat colour: | grey |
Outer diameter approx.: | 50 mm |
Conductor class: | Class 5 = fine-wire |
Stranding element: | no |
Material of the core insulation: | Polyvinyl chloride (PVC) |
Core marking: | numbers |
Protective conductor: | yes |
Shield over stranding element: | without |
Shield over stranding: | Braid |
Support element: | without |
Sheath material: | Polyvinyl chloride (PVC) |
Torsion protection: | no |
Halogen-free in accordance with EN 60754-1/2: | no |
Flame-retardant: | in accordance with EN 60332-1-2 |
Low smoke in accordance with EN 61034-2: | no |
Cold-resistant according to EN 60811-504+505+506: | yes |
Oil-resistant according to EN 60811-404: | yes |
Permissible external cable temperature during assembly/handling: | -5 to 70 °C |
Permissible External cable temperature after installation without vibration: | -40 to 70 °C |
Nominal voltage U0: | 300 V |
Nominal voltage U: | 500 V |
AWG size: | 000 |
Shape: | round |
Min. permissible bending radius, flexible use/free movement: | 1000 mm |
Min. permissible bending radius, stationary use/fixed installation: | 300 mm |