Description
Features
Reviews
Surge protection for a signal circuit operated without earth potential in a screw-on module with protection class IP67 for sensor heads, connection ½ inch 14 NPT. Tested according to ignition protection types in Ex areas Ex d / Ex tD / Ex ia IIC / Ex iaD. Is suitable for use in the field bus system according to the FISCO concept, HART-capable.
| Property | Value |
| Signaling on the device: | without |
| Nominal discharge current (8/20): | 10 kA |
| Maximum continuous voltage DC: | 36 V |
| Maximum continuous voltage AC: | 25 V |
| Protection level wire/wire: | 65 V |
| Protection level wire/earth: | 1100 V |
| With remote signaling contact: | no |
| Explosion-tested version: | yes |
| Nominal voltage DC: | 24 V |
Features
Explosion-tested version
Yes
With remote signaling contact
No
Highest continuous voltage DC
36 V
Nominal voltage DC
24 V
Protection level wire/wire
65 V
Protection level wire/earth
1100 V
HAB
S-PT-EX-24DC-1/2'
Manufacturer
HAN
2800035
GTIN
4046356411011
Highest continuous voltage AC
25V
Nominal discharge current (8/20)
10kA
Signaling on the device
Without