Description
Features
Reviews
Networkable hybrid motor starter for reversing 3~ AC motors up to 500 V AC and 3 A output current, with adjustable overload shutdown, emergency stop function up to SIL 3 / PL e and screw connection, DIN rail bus connector is included.
| Property | Value |
| Overload release current setting: | 0.18 to 3 A |
| Voltage type for actuation: | DC |
| Connection type main circuit: | Screw connection |
| Rated operating current Ie: | 3 A |
| Rated control supply voltage Us at DC: | 19.2 V |
| With short-circuit release: | no |
| Protection class (IP): | IP20 |
| Design of electrical connection for auxiliary and control circuit: | Screw connection |
| Trigger class: | CLASS 10 |
| Type of motor starter: | Reversing starter |
| Rail mounting possible: | yes |
| Suitable for EMERGENCY STOP: | yes |
| Width: | 22.5 mm |
| Height: | 107 mm |
| Depth: | 114 mm |
Features
Rated operating current Ie
3 A
Design of electrical connection for auxiliary and control circuit
Screw connection
Type of motor starter
Reversing starter
With short-circuit release
No
HAB
ELR H5-IES-SC/500AC-3-IFS
Manufacturer
HAN
2905152
GTIN
4046356920339
Connection type main circuit
Screw connection
Trigger class
CLASS 10
Rated control supply voltage Us at DC
19.2V
Width
22.5 mm
Suitable for EMERGENCY STOP
Yes
Height
107 mm
IP protection)
IP20
Voltage type for actuation
DC
Depth
114 mm
Mounting rail possible
Yes
Overload release current setting
0.18 to 3 A