Space-saving installation thanks to narrow width of 6.2 mm. Signaling without additional auxiliary power thanks to mechanical status display. Optional remote signaling module monitors up to 40 items without additional wiring. No influence on the signal during maintenance work thanks to impedance-neutral plugging and unplugging of the protective plugs. Error-free replacement of protective plugs thanks to coding. Simple interruption of signal circuits for maintenance work thanks to vertical blade separation. Safe behavior in the event of overload thanks to integrated disconnection device. Grounded or insulated shield grounding thanks to third terminal point on the surge protection device. Worldwide use in potentially explosive areas thanks to ATEX and IECEx approvals.
Property | Value |
Signaling on the device: | optical |
Mounting type: | other |
Nominal discharge current (8/20): | 5 kA |
Nominal load current: | 0.6 A |
Connection 1: | Terminal |
Maximum continuous voltage DC: | 15 V |
Protection level wire/wire: | 145 V |
Protection level wire/earth: | 1100 V |
Protection level wire/signal ground: | 95 V |
With remote signaling contact: | no |
Explosion-tested version: | yes |
Nominal voltage DC: | 12 V |