Surge protection Acti 9 - Type 2. iPRD40, without remote signaling contact, 4-pole, 3P+N, TT & TNS, Imax 40kA. iPRD surge arresters are used to protect low-voltage consumer systems and equipment against transient overvoltages caused by remote lightning strikes, switching operations or electrostatic discharges. Type 2: powerful arrester for use in systems that are regularly exposed to transient overvoltages.
| Property | Value |
| Protection level: | 1.4 kV |
| Nominal discharge current (8/20): | 15.0 kA |
| Highest continuous voltage AC: | 350.0 V |
| Nominal voltage AC: | 400.0 V |
| Protection level LN: | 1.4 kV |
| Mounting type: | DIN rail TH35 |
| Size: | 4 TE |
| Signaling on the device: | optical |
| With remote signaling contact: | no |
| Test class type 2: | yes |
| Max. conductor cross-section flexible (fine-stranded): | 35.0 mm² |
| Max. Conductor cross-section rigid (single/multi-wire): | 35.0 mm² |
| Protection level N-PE: | 1.4 kV |
| Integrated backup fuse: | no |
| Protection class (IP): | IP20 |
| Network type DC: | no |
| Network type IT: | no |
| Network type TN: | no |
| Network type TN-C: | no |
| Network type TN-CS: | no |
| Network type TN-S: | yes |
| Network type TT: | yes |
| Network type other: | no |
| Number of conductors (excluding earth): | 4.0 |
| Short-circuit strength (Isccr): | 50.0 kA |
| Max. discharge current (8/20): | 40.0 kA |
| Max. Overcurrent protection device branch wiring (fuse): | 63.0 A |
| Max. overcurrent protection device V-wiring (fuse): | 80.0 A |
| Integrated short-circuit protection: | no |
| Leakage current free: | no |
Features
Max. conductor cross-section rigid (single/multi-wire)
35.0 mm²
Max. conductor cross-section flexible (fine-stranded)
35.0 mm²
Protection level
1.4 kV
With remote signaling contact
No
Number of conductors (excluding earth)
4.0
Network form TT
Yes
Network type TN-S
Yes
Max. discharge current (8/20)
40.0 kA
Test class type 2
Yes
Network form TN
No
Network type TN-C
No
Network type TN-C-S
No
Short circuit strength (Isccr)
50.0 kA
Protection level L-N
1.4 kV
Network type DC
No
Protection level N-PE
1.4 kV
Integrated backup fuse
No
Network type IT
No
HAB
TYPE2 iPRD40 3P+N
Manufacturer
HAN
A9L40600
GTIN
3606480506383
Size
4 HP
Highest continuous voltage AC
350.0V
Mounting type
DIN rail TH35
Nominal discharge current (8/20)
15.0kA
Nominal voltage AC
400.0V
IP protection)
IP20
Signaling on the device
Optical