Miniature circuit breaker C60H-DC, 2P, 16A, C-characteristic, . Product range: C60 - Product or component type: Miniature circuit breaker - Device short name: C60H-DC - Network type: DC - Trip unit technology: thermomagnetic - Interrupting capacity: 10 kA Icu according to EN 60947-2 - 440V DC, 10 kA Icu according to IEC 60947-2 - 440V DC, 20 kA Icu according to GB 14048.2 - 220V DC, 20 kA Icu according to GB 14048.2 - 250V DC, 20 kA Icu according to IEC 60947-2 - 220V DC, 20 kA Icu according to IEC 60947-2 - 250V DC, 6 kA Icu according to EN 60947-2 - 500V DC, 6 kA Icu according to IEC 60947-2 - 500V DC - Usage category: Category A according to EN 60947-2, Category A according to IEC 60947-2 - Suitability for insulation: yes according to EN 60947-2, yes according to IEC 60947-2.
Property | Value |
Tripping characteristic: | C |
Rated current: | 16.0 A |
Rated voltage: | 440.0 V |
Type of voltage: | DC |
TE: | 2.0 |
Number of poles (total): | 2.0 |
Additional equipment possible: | yes |
Overvoltage category: | 4.0 |
Installation depth: | 44.0 mm |
Protection class (IP): | IP20 |
Degree of pollution: | 3.0 |
Switching neutral conductor: | no |
Number of protected poles: | 2.0 |
Flush-mounted installation: | no |
Rated insulation voltage Ui: | 500.0 V |
Rated impulse withstand voltage Uimp: | 6.0 kV |
Ambient temperature during operation: | -25.0 to 70.0 °C |
Connectable conductor cross-section, stranded: | 1.0 to 16.0 mm² |
Connectable conductor cross-section, single-wire: | 1.0 to 25.0 mm² |
Explosion-proof: | no |