Residual current circuit breaker, all-current sensitive, for electric charging station Acti 9 iID. 2-pole, nominal current 25A, type B-EV, nominal residual current 30mA, operating voltage (Ue) 230 AC, 50Hz, insulation voltage 250V AC. Snap action for low-wear switching of the contacts. With mechanical front-side fault signal indicator (VisiTrip) to indicate tripping due to residual current. Safe contact indicator (VisiSafe) of the residual current circuit breaker, green indicator ensures that there is no voltage on the output side. Test button for regular function testing. Double connection terminals for connecting cables or phase rails on both sides. Easy removal of the individual device when the phase rail is installed, thanks to the fastening element accessible from the front. Additional auxiliary modules that can be connected in series (optional) undervoltage release (iMN), overvoltage release (iMSU), shunt release (iMX), auxiliary switch for status reporting (iOF), fault reporting switch (iSD). Protection of charging stations for electric vehicles. Color RAL 9003. Meets the following standards IEC/EN 61008-2-1,IEC/EN 62423,IEC 61543 0664.
| Property | Value |
| Rated voltage: | 230.0 V |
| Current: | 25.0 A |
| Fault current: | 0.03 A |
| Mounting type: | DIN rail |
| Protection class (IP): | IP20 |
| Frequency: | 50 Hz |
| Number of poles: | 2.0 |
| TE: | 4.0 |
| Selective type: | no |
| Residual current type: | B |
| Additional equipment possible: | yes |
| Installation depth: | 44.0 mm |
| Surge current strength: | 3.0 kA |
| Short-term delayed Type: | no |
| Rated insulation voltage Ui: | 250.0 V |
| Rated impulse withstand voltage Uimp: | 6.0 kV |
| With locking device: | no |
| Ambient temperature during operation: | -25.0 to 60.0 °C |
| Pollution level: | 3.0 |
| Connectable conductor cross-section, stranded: | 1.0 to 25.0 mm² |
| Connectable conductor cross-section, single-wire: | 1.0 to 35.0 mm² |
| Voltage type: | AC |
| Explosion-proof: | no |








