The Altivar ATS480 soft starter is designed for starting and stopping asynchronous motors with voltages from 208V to 690V. It meets the requirements of the most demanding applications in normal and heavy use. With a rated current of 320A at normal overload, it operates motors from 90kW to 315kW according to the mains voltage. Designed for digitalization, connected, optimized to comply with cybersecurity standards, it simplifies project execution and maximizes application availability. Its torque control (TCS) masters acceleration and deceleration. Thanks to dynamic braking and DC injection, high inertia applications are efficiently managed. It can be connected in the motor line or in delta connection to reduce the operating current. The embedded test routine simplifies commissioning in delta connection. The dimensions are 320mm (width) x 277mm (depth) x 380mm (height) and the weight is 18.2kg. The Altivar soft starter ATS480 was developed to monitor processes, infrastructures and industrial machines. It is compliant with IEC/EN60947-4-1. It is certified according to cULus, UKCA, CCC, RCM, EAC, and marine certified according to DNV, ABS, BV and CCS. Operator terminals, remote mounting kit and communication modules are standard with the Altivar drives. Line chokes and DNV kits are identical to the predecessor ATS48. ATS480 is compatible with ATS48, it has the same footprint, mounting, torque control, I/O, menus... The integration of the Altivar soft starter ATS480 into EcoStruxure drastically simplifies the selection of architecture, detailed design and execution of ventilation and electrical systems. It is a Green Premium product, designed to take into account environmental aspects beyond current directives and regulations, and is compliant with RoHS and REACH.
Property | Value |
Rated power three-phase motor, inside-delta connection, at 230 V: | 160.0 kW |
Integrated motor overload protection: | yes |
Rated power three-phase motor, standard connection, at 230 V: | 90.0 kW |
Rated ambient temperature without derating: | 40.0 °C |
Rated power three-phase motor, standard circuit, at 400 V: | 160.0 kW |
Rated power three-phase motor, inside-delta circuit, at 400 V: | 250.0 kW |
Rated operating current Ie at 40 °C Tu: | 320.0 A |
Type of voltage for actuation: | AC |
Rated operating voltage Ue: | 208.0 to 690.0 V |
Rated control supply voltage AC 50 Hz: | 208.0 to 690.0 V |
Rated control supply voltage AC 60 Hz: | 208.0 to 690.0 V |
Torque control: | yes |
Internal bridging: | no |
With display: | no |
Function: | one direction of rotation |
Trip class: | other |
Protection class (IP): | IP00 |