ComPacT NSXm100N is a complete 3P fixed circuit breaker designed to optimize space and breaking capacity. The breaking capacity (Icu) is 50 kA rms at 415 VAC, 50/60 Hz. The operating voltage is 440 VAC 50/60 Hz. It introduces new features such as EverLink connection technology. It offers built-in DIN rail and panel mounting capabilities as well as additional equipment with spring terminals that are externally visible. This 3-pole residual current circuit breaker (RCD) is one of the smallest on the market. The dimensions are 108 mm (W) x 144 mm (H) x 80 mm (D). It ensures conformity with international standards (IEC 60947/CCC/EAC) and marine specifications.
Property | Value |
Rated continuous current Iu: | 100.0 A |
Connection type main circuit: | Screw connection |
Number of poles: | 3.0 |
Auxiliary normally open contact: | 0.0 |
Auxiliary normally closed contact: | 0.0 |
Device design: | Built-in device Fixed installation technology |
Position of the connection for the main circuit: | front |
Protection class (IP): | IP40 |
Overload release current setting: | 40.0 to 100.0 A |
Setting range of the short-time delayed short-circuit release: | 60.0 to 1000.0 A |
Setting range of the undelayed short-circuit release: | 1500.0 A |
Rated voltage: | 440.0 V |
Icu at 400V: | 50.0 kA |
Suitable for DIN rail mounting: | yes |
Design of the actuating element: | toggle |
Integrated earth fault protection: | yes |
Motor drive integrated: | no |
Motor drive optional: | no |
With trip detector: | yes |
Number of auxiliary contacts as changeover contacts: | 0.0 |
Complete device with protection unit: | yes |
DIN rail mounting optional: | no |
Features
Number of auxiliary contacts as changeover contacts
0.0
HAB
NSXM VIGI 100A 3P 50KA/415V ELINK
Manufacturer
HAN
C11N34V100L
GTIN
3606481992864
Connection type main circuit
Screw connection
Design of the actuating element
Gag
Rated continuous current Iu
100.0A
Rated voltage
440.0V
Setting range of the short-time delayed short-circuit release
60.0 to 1000.0 A
Setting range of the instantaneous short-circuit release
1500.0A
Suitable for DIN rail mounting
Yes
Device type
Built-in device Fixed installation technology
DIN rail mounting optional
No
Integrated earth fault protection
Yes
Complete device with protection unit
Yes
With trip detector
Yes
Motor drive integrated
No
Motor drive optional
No
Number of poles
3.0
Position of the connection for main circuit
In front
IP protection)
IP40
Overload release current setting
40.0 to 100.0A