Description
Features
Reviews
Fuse switch disconnector The use of fuses is a reliable and effective solution for protecting your low-voltage equipment against short circuits
Property | Value |
Rated continuous current Iu: | 630.0 A |
Degree of protection (IP), front: | IP20 |
Number of poles: | 4.0 |
Design as main switch: | yes |
Design of the actuating element: | without actuator |
Type of connection main circuit: | Screw connection |
Suitable for front mounting: | no |
Suitable for floor mounting: | no |
With fuse monitoring: | no |
Version as EMERGENCY STOP device: | no |
Conditional rated short-circuit current Iq: | 100.0 kA |
Version as safety switch: | no |
Max. Rated operating voltage Ue at AC: | 1000.0 V |
Suitable for busbar construction: | yes |
Suitable for fuse links: | NH3 |
Position of the actuating element: | left |
Integrated motor drive: | no |
Rated short-time withstand current Icw: | 100.0 kA |
Optional motor drive: | no |
Rated operating power at AC-23, 400 V: | 355.0 kW |
Cable entry: | other |
Equipped with connectors: | no |
Features
HAB
M. fuses TeSys GS2S 4p 630A DIN 3
Manufacturer
HAN
GS2SG4
GTIN
3389119411080
Connection type main circuit
Screw connection
Designed as main switch
Yes
Designed as an EMERGENCY STOP device
No
Designed as a safety switch
No
Design of the actuating element
Without actuator
Conditional rated short-circuit current Iq
100.0kA
Rated operational power at AC-23, 400 V
355.0kW
Rated continuous current Iu
630.0A
Rated short-time withstand current Icw
100.0kA
Suitable for floor mounting
No
Suitable for front mounting
No
Suitable for busbar construction
Yes
Suitable for fuse inserts
NH3
Cable entry
Other
Max. rated operating voltage Ue at AC
1000.0V
With fuse monitoring
No
Equipped with connectors
No
Motor drive integrated
No
Motor drive optional
No
Number of poles
4.0
Position of the actuator
Left
Protection class (IP), front
IP20
No reviews yet — your comment may be first.
All reviews 0