Description
Features
Reviews
Load-break switches A range of safety control products that are easy to use and set up, with compact and ergonomic products for starter motor and stop motor requirements.
Feature | Value |
Number of poles: | 3.0 |
Operating power: | 5.5 kW |
Number of auxiliary contacts as normally closed: | 0.0 |
Number of auxiliary contacts as normally open: | 0.0 |
Number of auxiliary contacts as changeover: | 0.0 |
Rated continuous current Iu: | 20.0 A |
Max. Rated operating voltage Ue at AC: | 690.0 V |
Design as EMERGENCY STOP device: | yes |
Protection class (IP), front: | IP65 |
Connection type main circuit: | Screw connection |
Device design: | Built-in device, fixed installation technology |
Design of the actuating element: | short rotary handle |
Suitable for floor mounting: | no |
Conditional Rated short-circuit current Iq: | 6.0 kA |
Integrated motor drive: | no |
Suitable for 4-hole front mounting: | no |
Version as maintenance/repair switch: | no |
Voltage release optional: | no |
Suitable for central front mounting: | yes |
Suitable for intermediate installation: | no |
Suitable for distribution board installation: | no |
Design as main switch: | yes |
Design as safety switch: | no |
Motor drive optional: | no |
Lockable: | yes |
Design as reversing switch: | no |
Rated short-time withstand current Icw: | 0.14 kA |
Color of the actuating element: | red |
Rated operating voltage: | 690.0 V |
Rated operating power at AC-3, 400 V: | 4.0 kW |
Rated continuous current at AC-21, 400 V: | 20.0 A |
Number of switches: | 1.0 |
Rated continuous current at AC-23, 400 V: | 11.0 A |
Features
Number of auxiliary contacts as changeover contacts
0.0
HAB
VCDN20
Manufacturer
HAN
VCDN20
GTIN
3389110759914
Connection type main circuit
Screw connection
Number of auxiliary contacts as normally open
0.0
Number of auxiliary contacts as normally closed
0.0
Number of switches
1.0
Designed as main switch
Yes
Designed as an EMERGENCY STOP device
Yes
Designed as a safety switch
No
Designed as a maintenance/repair switch
No
Version as reversing switch
No
Design of the actuating element
Short twist grip
Conditional rated short-circuit current Iq
6.0kA
Rated operational power at AC-3, 400 V
4.0kW
Rated operating voltage
690.0V
Rated continuous current Iu
20.0A
Rated continuous current at AC-21, 400 V
20.0A
Rated continuous current at AC-23, 400 V
11.0A
Rated short-time withstand current Icw
0.14kA
Color of the actuator
Red
Suitable for floor mounting
No
Suitable for front mounting 4-hole
No
Suitable for front mounting Central
Yes
Suitable for distribution board installation
No
Suitable for intermediate construction
No
Device type
Built-in device Fixed installation technology
Max. rated operating voltage Ue at AC
690.0V
Motor drive integrated
No
Motor drive optional
No
Number of poles
3.0
Protection class (IP), front
IP65
Voltage release optional
No
Lockable
Yes
No reviews yet — your comment may be first.