Circuit breaker 3VA5 UL Frame 250 switching capacity class M 35kA @ 480V 2-pole, system protection TM210, FTFM, In=175A overload protection Ir=175A fixed short-circuit protection Ii=10 x In without connection 3VA5 molded case circuit breaker for system protection, UL approval. The 3VA UL molded case circuit breakers from Siemens, as an important component of the SENTRON protection components for industrial applications and for applications in the infrastructure sector, offer effective system and starter protection by safely switching off in the event of overload and short circuit. The 3VA UL sets standards in flexibility and modular accessories. The 3VA UL molded case circuit breaker also offers the best conditions for machine and switchgear manufacturers exporting worldwide. In addition to the IEC standard, the two series 3VA5 and 3VA6 also meet the UL standard. All functions can therefore be used and implemented for systems worldwide. This variant of the 3VA molded case circuit breaker is characterized by: 1. Compact design. 2. Available as a variant for system protection. 3. Depending on the size: 1-, 2- (3-pole housing design) and 3-pole versions. 4. Depending on the size: Switching capacity of 25 kA - 100 kA at 480 V for 3-pole switches and 25 kA - 50 kA at 277 V for 1-pole switches. 5. The series has a thermal-magnetic overcurrent release. 6. Modular and easy-to-install internal accessories with a wide range of functions. 7. Consistent accessories platform for all 3VA UL molded case circuit breakers. www.siemens.de/3VA. Siemens offers a comprehensive portfolio of protection, switching, measuring and monitoring devices, distribution systems as well as switches and sockets for safe, efficient electrical infrastructure in buildings and industry.
Property | Value |
Rated continuous current Iu: | 175 A |
Number of poles: | 2 |
Degree of protection (IP): | IP40 |
Overload release current setting: | 175 A |
Setting range of the instantaneous short-circuit release: | 1750 A |
Rated voltage: | 690 V |
Rated short-circuit breaking current Icu at 400 V, 50 Hz: | 55 kA |
Suitable for DIN rail mounting: | yes |
Integrated earth fault protection: | no |
Integrated motor drive: | no |
Optional motor drive: | yes |
With trip detector: | no |
Complete device with protection unit: | yes |
DIN rail mounting optional: | yes |