Circuit breaker 3VA6 UL Frame 400 3-pole, starter protection ETU310M, I, In=250A without overload protection short-circuit protection Ii=3...15 x In without connection molded case circuit breaker 3VA6 with 3-series ETU as motor circuit protector, UL approval. The molded case circuit breakers 3VA UL from Siemens as an important component of the SENTRON protection components for industrial applications as well as for applications in the infrastructure sector offer effective system and starter protection by safely switching off in the event of overload and short circuit. The 3VA sets standards in flexibility and modular accessories. The molded case circuit breaker 3VA UL also offers the best conditions for machine and switchgear manufacturers who export worldwide. In addition to the IEC standard, the two series 3VA5 and 3VA6 also meet the UL standard. All functions can therefore be used and implemented for systems worldwide. This variant of the 3VA molded case circuit breaker is characterized by: 1. Compact design. 2. Available as a motor circuit protector 3. Starter protection switch for protecting electric motors against short circuits. 4. Available as a 3-pole version. 5. Depending on size: Rated operating current from 25 A to 500 A. 6. Switching capacity 100kA at 480 V (SCCR without contactor) 7. The series has an electronic overcurrent release. 8. Installation in fixed installation, plug-in technology, withdrawable technology possible. 9. Modular and easy-to-install internal accessories with a wide range of functions. www.siemens.de/3VA. Siemens offers a comprehensive portfolio of protection, switching, measuring and monitoring devices, distribution systems as well as switches and sockets for safe, efficient electrical infrastructure in buildings and industry.
Property | Value |
Rated continuous current Iu: | 250 A |
Number of poles: | 3 |
Degree of protection (IP): | IP40 |
Setting range of the instantaneous short-circuit release: | 750 A |
Rated voltage: | 690 V |
Rated short-circuit breaking current Icu at 400 V, 50 Hz: | 110 kA |
Suitable for DIN rail mounting: | yes |
Integrated earth fault protection: | no |
Motor drive integrated: | no |
Motor drive optional: | yes |
With trip detector: | no |
Complete device with protection unit: | yes |
DIN rail mounting optional: | yes |