Voltage and frequency relay type UFR1001E

Product description

Network and system protection (NA protection) NA box according to VDE-AR-N 4105, 4110 and 4120, TOR generators, G98 and G99, DIN V0126-1-1 and others

The UFR1001E network decoupling relay monitors voltage and frequency in three-phase and alternating current networks.
It meets the conditions for central NA protection according to VDE-AR-N 4105:2018-11 in self-generation systems for feeding into the low-voltage network. For VDE-AR-N 4105:2018-11, corresponding parameters were stored in program 2 and the monitoring of the coupling switch and the protection of parameters were adjusted accordingly.

For feeding into the medium-voltage network according to VDE-AR-N 4110:2018-11, the UFR1001E is suitable as unit protection on the generating units and as intermediate decoupling protection. K2 is used as the live contact. It always switches with K1.
Use as higher-level decoupling protection only if no QU protection is required and after consultation with the network operator and certifier.

The device has a two-channel, single-fault protection design and therefore meets the requirements of VDE-AR-N 4105:2018-11. The function of the connected switch is monitored. When monitoring is activated, the device does not switch back on if a shutdown error is detected; if a switch-on error occurs, attempts are made to switch it back on, thus ensuring increased system availability.

Limit values ​​for different applications are preset. They can be easily changed, as far as permitted.
With a 2-stage test, both trip circuits can be tested separately and the switching time of connected coupling switches can be determined.
With the standby input, a remote shutdown can be implemented, e.g. with a ripple control receiver.

Under-/overvoltage monitoring 15 - 520 V (with voltage transformers up to 1,000 V)
Measurement against N and/or phase-phase
Under-/overfrequency monitoring 45 - 65 Hz
Monitoring of the voltage quality (10-minute average)
Vector surge monitoring 2…65° can be switched on
ROCOF, monitoring of frequency gradient df/dt 0.100...5,000 Hz/s
Monitoring of the zero voltage U0 (ANSI 59v0)
single-fault safe, with monitoring of the coupling switch (can be switched off at Use of the integrated coupling switches of PV and battery converters in accordance with DIN EN 62109 (VDE 0126-4))
2 restart attempts in the event of a coupling switch switch-on error
passive island network detection in accordance with Chapter 6.5.3 and Appendix D2
for use in isolation points for self-generation systems
Response time adjustable 0.05 ... 300.0 s
Switch-back time adjustable 0 ... 6,000 s
Default setting in accordance with VDE-AR-N 4105-2018-11 (Pr 2) and VDE-AR-N 4105-2011-08 (Pr 1)
Default setting in accordance with VDE-AR-N 4110-2018-11 (Pr 11-14) and bdew guideline (Pr 3-6)
Default setting in accordance with TOR Generator type A, B, C, D for Austria
Default setting according to Synergrid C10/C11 for Belgium
Default setting according to G98 (G83/2) and G99 (G59/3) for Great Britain
Default setting according to NA/EEA-NE7 CH 2020 for Switzerland
Alarm counter for 100 alarms (with trigger value, cause and relative time stamp)
Recording of the alarm total time
Standby input with counter and time memory
Test button and simulation function with measurement of the switch-off times
Sealing option and code protection for settings. The values ​​can also be read when sealed
Easy commissioning and programming thanks to preset basic programs
Control voltage AC/DC 24-270 V
Distribution installation housing V6, 6 TE, 105 mm wide, installation depth 66 mm
Accessories: Installation frame ER6 for control panel installation

Approvals and validated

Germany:
Proof of conformity NA protection VDE-AR-N 4105-2011-08 and 2018-11 'Self-generation systems on the low-voltage network'
Component certificate VDE-AR-N4110 and 4120
Proof of conformity NA protection according to BDEW guideline 'Self-generation systems on the medium-voltage network'
Europe:
Certificate of non-objection DIN V0126-1-1
Australia:
listed at Energex RED STD00233
Belgium:
listed at Synergrid C10/C11
Finland:
Certificate of non-objection SFS EN 50549-1:2019, SFS-EN 50549-2:2019
France:
Proof of conformity DIN V1256-1-1, VFR2013/VFR2014, ERDF-NOI-RES13E:2013-06
DIN V1256-1-1, VFR2019
Great Britain:
Proof of conformity G59/3:2013, G83/2:2012,
G99/1-1+2+3:2018 and G98/1-1+2:2018
Ireland:
Proof of conformity EN 50549-1:2019, EN 50438:2013
Japan:
accepted by Tepco
Netherlands:
EN50549-1
Austria:
TOR producer A,B,C,D
Certificate of non-objection ÖVE/ÖNORM E 8001-4-712:2009-12, Appendix A
South Africa:
Proof of conformity NRS 097-2-1:2010 1.0
Spain:
RD1699:2011 / RD413:2014

Technical data

Nominal connection
Control voltage Us AC/DC 24-270 V, 0/40...70 Hz, <,5VA , DC: 20.4...297 V, AC: 20.4...297 V

Output relay
Relay output 2 changeover contacts (data see operating instructions)

Voltage measurement
Measuring voltage phase - phase AC 15...530 V (<, 5 V is displayed as 0)
Setting range phase - phase AC 15...520 V
Measuring voltage phase - N AC 10...310 V (<, 5 V is displayed as 0)
Setting range phase - N AC 15...300 V
Measuring principle True RMS measurement both half-waves
Hysteresis adjustable 1.0...99.9 V
Measuring accuracy (with N) ±0.6% of measured value
Measuring accuracy (without N) ±0.8% of measured value
Display accuracy >,100V: -1 digit (resolution 1 V), <,100V: -1 digit (resolution 0.1 V)
Measuring functions 3-phase with /without N
Response time (dAL) adjustable 0.05 (± 15ms)...300.0 s
Switch-back time (doF) adjustable 0 (approx. 200 ms)...6,000 s

Frequency measurement
Frequency range 40...70 Hz
Setting range 45.00...65.00 Hz
Hysteresis 0.05...10.00 Hz
Response time (dAL) adjustable 0.05 (± 15ms)...300.0 s
Reset time (doF) adjustable 0 (>,200 ms)...6,000 s

Vector jump
Measuring range 0...90.0°
Setting range 2.0...65.0 °
Response time (dAL) <, 50 ms
Reset time (doF) adjustable 3...240 s
Delay at Us on adjustable 2...20 s

RoCoF df/dt
Setting range 0.100...5,000 Hz/s, 4...50 periods

Digital outputs (galvanically isolated)
Switching voltage I1 DC 4.5...27 V
Current Q1...Q5 max. 20 mA / output

Inputs protective feedback
Voltage Y0...Y1/2 DC 15...35 V
Switching time (coupling switch) adjustable 0.5...99.0 s

Test conditions (EN 60255)
Rated impulse withstand voltage 4000 V
Overvoltage category III
Pollution degree 2
Rated insulation voltage Ui 300 V
Duty cycle 100 %
Permissible ambient temperature -20 °C...+55 °C
Storage temperature -25 °C...+70 °C
Climate class (IEC/EN 60721-3-3) 3K5 (without condensation, without ice formation)
EMC interference immunity EN 61 000-6-2
EMC interference emission EN 61 000-6-3

Housing
Housing / mounting frame design V6 / mounting frame ER6, 6 TE
Dimensions H x W x D 90 x 105 x 58 [mm], installation depth 55 mm
Cable connection single-wire 1 x 4 mm2 each
Fine-wire with Wire end ferrule 1 x 2.5 mm2 each
Protection class housing/terminals IP30/20
Fastening snap fastening on 35 mm mounting rail in accordance with EN
60 715 or screw fastening M4
Weight approx. 250 g